aumüller
ferralux®
Smoke and heat ventilation

aumüller ferralux®
Smoke and heat ventilation

RWA1000 Hardware systems
Functional universal geniuses
AUMÜLLER RWA1000 hardware systems from AUMÜLLER can be used for inward-opening side-hung, bottom-hung or top-hung windows. With the aid of a sequence control, the window is first unlocked, and then opened by one or more window drives. When closing, the window is first closed by the window drive and then locked by the window locking drive.
Features
The main features of the RWA hardware systems are determined by the combination of window drive, window locking drive, fastening elements and fitting position.
A selection of combination possibilities and the achievable performance features of bottom-hung and top-hung windows can be found in the following table. We will be happy to put together further combination possibilities tailored to your requirements on the principle of the RWA hardware systems. Please feel free to contact us for this information.
RWA1000 Mounting
AUMÜLLER RWA1000 hardware systems can be used in SHEV systems and for natural ventilation via automated windows in façades.
RWA1000 hardware systems are intended for inward-opening windows.
The drive is mounted to the window frame with a triangular bracket and a casement bracket on the window frame of the side closing edge. It lies at an acute angle to the window frame. The effective drive force in the opening direction of the window depends on the angle of attack. Larger angles of attack are preferable. This must be taken into account in the arrangement of the window drives, particularly when used with a top-hung window. For large and heavy windows, 2 window drives are required, one per side closing edge. The following apply as guideline dimensions:
- The seating angle of attack between the window frame and window drive should not be less than 12°
- The distance between the central axis of the casement bracket and the hinge axis (rotation point) should not be less than 1/3 of the corresponding window size
- For window height larger than 1300 mm, 2 window drives are required
- The space required at the frame is 40 mm
The locking drive is mounted irrespective of the width and length of the window frame, on the frame of the main closing or side closing edge. Installation details and corresponding accessories ca be found in the technical documentation.
The locking of the window takes place according to the window locking drive used by means of locking angles, or by an additional locking roller, or directly via the gear box of the proven window fitting. The features tested according to EN14351-1, such as integrity in driving rain and joint permeability of the window over the complete joint length are thereby usually maintained.
The main users of RWA fitting systems are window and façade fitters.
The linked product series describe only some of the possible combinations of window drives and window locking drives with fastening elements. We will be happy to put together further combination possibilities tailored to your requirements on the principle of the RWA hardware systems. Please feel free to contact us for this information.
Downloads
Product information
Data sheet
RWA1000 + PL10 S1 / FV3Data sheet
RWA1000 + PL10 S1 / OFV1Data sheet
RWA1000-TE + PL10 S1 / FV1Data sheet
RWA1000-TE + PL10 S1 / OFV 1 / USKM
Technical information
Insatallation Instructions
PL / RWA SystemsDimensions
RWA1000Mounting examples
RWA hardware systems
Certificates
Declaration of Conformity
RWA1000Environmental product declaration
EPD drives